Advanced application of transient stability constrained-optimal power flow to a transmission system including an HVDC-LCC link

Ignacio A. Calle, Pablo Ledesma, Edgardo D. Castronuovo

Research output: Contribution to journalArticle

13 Citations (Scopus)

Abstract

© 2015 The Institution of Engineering and Technology. In this study, a transient stability constrained-optimal power flow (TSC-OPF) model is proposed and applied to a real case in the currently interconnected Balearic Islands-Iberian Peninsula system. The TSC-OPF retains the dynamics of all generators in the islands with fourth degree transient synchronous generator models and includes a representation of a high-voltage direct current (HVDC) link on the inverter side. The proposed large-scale non-linear optimisation problem, programmed in GAMS and solved using the CONOPT tool, is used to assess the economic impact of the HVDC on the Balearic Islands generation cost under different circumstances, using TSC-OPF and traditional OPF on the dispatch. Different recovery patterns of the HVDC link after a severe fault in the transmission grid are evaluated from the viewpoint of the cost and stability of power generation.
Original languageEnglish
Pages (from-to)1765-1772
Number of pages8
JournalIET Generation, Transmission and Distribution
DOIs
Publication statusPublished - 1 Jan 2015

Fingerprint Dive into the research topics of 'Advanced application of transient stability constrained-optimal power flow to a transmission system including an HVDC-LCC link'. Together they form a unique fingerprint.